Answer
Apr 27, 2022 - 09:18 AM
The AC-12 on the side the Kacon B30-81R emergency stop switch is the type of load it can handle. AC-12 is one of the Load characteristics and utilization categories in IEC product standard 60947-5-1. It indicates control of resistive loads and solid-state loads with isolation by optocouplers.