Answer
Sep 20, 2021 - 09:26 AM
Yes, you can program a user input to act as a timer reset on the Red Lion PAXCK010 panel meter. Depending on the timer, you can also stop/start programming using the same input that would stop/start the timer cycle to do a reset as well.
To program this panel meter:
In Menu 2-FNC program one of the three user inputs as a timer reset.
Press the PAR button for three seconds, PRO/NO should appear.
Press the up arrow twice to see 2-FNC
Press the PAR button to select one of the three available user inputs.
Press the up arrow once the user input is selected until you see RST-E
Press the PAR button and set T-DSP to Yes.
Press the PAR button several times to exit program mode. You will see Pro/no then PRO/ END.
For your convenience, the user manual is also linked below:
Red Lion PAXCK010 User Manual
To program this panel meter:
In Menu 2-FNC program one of the three user inputs as a timer reset.
Press the PAR button for three seconds, PRO/NO should appear.
Press the up arrow twice to see 2-FNC
Press the PAR button to select one of the three available user inputs.
Press the up arrow once the user input is selected until you see RST-E
Press the PAR button and set T-DSP to Yes.
Press the PAR button several times to exit program mode. You will see Pro/no then PRO/ END.
For your convenience, the user manual is also linked below:
Red Lion PAXCK010 User Manual